• (0)

TESYS DECA CIRCUIT BREAKER THERMAL MAGNETIC 3P 0.25-0.40A SPRING

GV2ME033
2414196

Sign in to view price

TeSys GV motor circuit breaker, 3 poles (3P), 0.4A/690V, for 3-phase motor applications 0.09kW@400V. It provides a thermal-magnetic protection with a thermal setting range 0.25-0.4A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Connection by spring terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
schneider-gv2me033_Datasheet1
  • All returns must be made within 7 days of purchase.
  • Valid receipt is required for all returns.
  • Click Here to view the return policy.
Available Shipping Methods:

Product Overview

Product ID:
2414196
Manufacturer Part Number:
GV2ME033
EAN:
3389110346374
Brand/Manufacturer
SCHNEIDER ELECTRIC
Unit of Measure:
PCS

Specification

Adjustment range undelayed short-circuit release:
5...5 A
Degree of protection (IP):
IP20
Depth:
78.2 mm
Device construction:
Complete device in housing
Height:
101 mm
Number of poles:
3
Overload release current setting:
0.25...0.4 A
Phase failure sensitive:
yes
Rated operating voltage:
690...690 V
Rated operation power at AC-3, 230 V:
0.06 kW
Rated operation power at AC-3, 400 V:
0.09 kW
Rated permanent current Iu:
0.4 A
Rated short-circuit breaking capacity Icu at 400 V, AC:
100 kA
Switch off technique:
Thermomagnetic
Type of control element:
Push button
Type of electrical connection of main circuit:
Spring clamp connection
Width:
44.5 mm
With integrated auxiliary switch:
no
With integrated under voltage release:
no
With thermal overload protection:
yes