• (0)
ABB

S282UC-K6 MCB 6A 2P 6KA K CURVE

GHS2820164R0377
2049385

Sign in to view price

System pro M S280UC is a universal current miniature circuit breaker that provides current limitation. With its high DC voltage rating it is a excellent solution for DC applications in photovoltaic’s, telecommunication, traction and industrial applications.\nThey have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,K,Z), configurations (1P,2P,3P,4P), breaking capacities (up to 6 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S280UC comply with IEC/EN 60947-2, UL1077 and CSA 22.2 No. 235, allowing the use for commercial and industrial applications in direct current circuits for voltages up to 220 V DC 1 pole and 440 V DC 2, 3 and 4 poles.
abb-S282UC-K06A
  • All returns must be made within 7 days of purchase.
  • Valid receipt is required for all returns.
  • Click Here to view the return policy.
Available Shipping Methods:

Product Overview

Product ID:
2049385
Manufacturer Part Number:
GHS2820164R0377
EAN:
4012233637003
Brand/Manufacturer
ABB
Unit of Measure:
PCS

Specification

Additional equipment possible:
yes
Ambient temperature during operating:
-25...55 °C
Built-in depth:
68 mm
Concurrently switching neutral conductor:
no
Connectable conductor cross section multi-wired:
0.75...16 mm²
Connectable conductor cross section solid-core:
0.75...25 mm²
Current limiting class:
3
Degree of protection (IP):
IP20
Flush-mounted installation:
no
Frequency:
50...60 Hz
Number of poles (total):
2
Number of protected poles:
2
Over voltage category:
3
Pollution degree:
2
Rated current:
6 A
Rated impulse withstand voltage Uimp:
4 kV
Rated insulation voltage Ui:
500 V
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V:
10 kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V:
6 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V:
6 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V:
6 kA
Rated voltage:
440 V
Release characteristic:
K
Voltage type:
AC/DC
Width in number of modular spacings:
2